Self-Locking and Braking for Electric Linear Actuators: Holding Load Without Power
Will an actuator creep down after a power cut? It is a commonly overlooked question, and a lift table that drifts when power fails can scrap parts or trap a hand. The answer depends on screw type, lead angle, load direction and whether a separate brake is fitted.
1. Self-locking is not braking
Self-locking is a property of the drive pair: with power off, the load cannot back-drive the screw. A brake is a separate device: a spring clamps a disc onto the motor shaft when power is removed. Either can be used alone, or together. Many failures come from treating self-locking as rigid. It only guarantees static holding; vibration, shock and temperature change still cause slow creep.
2. Trapezoidal screws lock through lead angle
On a trapezoidal screw the lead angle is usually smaller than the equivalent friction angle, so friction exceeds the axial load component and the pair stalls. Efficiency is typically 20 to 40 percent, and that loss is exactly where self-locking comes from. Check the lead-to-diameter ratio: a small lead on a large diameter locks more reliably, and a fine-pitch unit will not back-drive within its rated load.
3. Ball screws are efficient and usually not self-locking
Ball screws roll instead of slide, reach efficiency above 90 percent, and resist back-driving poorly. On an electric linear actuator chosen for efficiency and life, the load will turn the screw when power is removed, so fit an electromagnetic brake or a mechanical lock. A second mistake: a trapezoidal screw that holds statically can still creep under vibration, because the thread flanks separate momentarily. Over weeks the movement can reach several millimetres.
4. Four braking options
The first is a fail-safe electromagnetic brake on the motor tail, engaging when power is cut, good for lifting and tilting loads; size static torque above the reflected load torque with 1.5 times margin. Second, a worm gearbox locks through sliding friction, compact but inefficient. Third, a mechanical pin or ratchet locks the rod directly, giving the highest holding force but needing the stroke to reach position first. Fourth, preloaded double nuts reduce creep passively in vibrating equipment. Cost rises in that order; match the option to the risk.
5. Plan the control side
The brake stops motion; the control decides how it stops. Limit switches should cut power just before the end of stroke to avoid continuous stall. An encoder version can re-home after power returns, and critical equipment can use a UPS to complete one retract stroke. For ventilation windows, check fire code: opening or closing on power loss reverses the brake and spring arrangement.
6. Verify, do not just read the datasheet
Test holding in the real load direction. Raise the actuator to mid-stroke under rated load, remove power for 24 hours and measure displacement; repeat with vibration or realistic shock. Log brake temperature and noise so a dragging brake does not overheat. For lift table and industrial door projects, Changzhou LOUIE Electric Linear Actuator runs this power-off holding test and records the displacement in the acceptance report.
7. Selection checklist
State load and direction, whether holding without power is required, acceptable creep, stroke, speed, cycles per day, mounting attitude, vibration, temperature and any safety code. Where absolute holding matters, use a trapezoidal screw with a fail-safe brake; where efficiency and life dominate, use a ball screw with a brake. Ask for the static torque and lead-angle calculation, and LOUIE Electric Linear Actuator selection stays on track.
Holding position after a power cut is both a mechanics and a safety question. Treat self-locking, braking and control as three layers, and back the choice with measured data rather than one word on a datasheet.