Powering an Electric Linear Actuator: Current, Cable and Fuse Sizing

From:Changzhou Louis Electric Push Rod Co., Ltd.  Time:2026/10/11 14:01:23  HIts:

Sizing the power supply is the step most machine builders rush. They match thrust and stroke, then discover the actuator is weak on start-up, the fuse blows, or the cable gets hot. This guide walks through current, voltage, cable size and fusing in the order you should choose them.

1. Why actuator power sizing gets overlooked

A linear actuator is an inductive load: inrush current on start-up can be double the running current or more. If you size the supply from the rating plate alone, it runs fine until a start, a stall or a cold morning pushes the current up. In LOUIE Electric Linear Actuator projects, most “weak unit” or “stops after a few seconds” complaints trace back to the supply and wiring rather than the actuator itself.

2. Start with current, not power

Actuator current changes with load. No-load current is low, rated-load current is in the datasheet, and stall current is higher still. Size for the number of actuators running at once times the rated current, and add the start-up peak; if several units move together, the currents add. A 24V DC actuator commonly draws a few amps to the mid-teens at rated load, but always read the datasheet rather than guessing.

3. Choosing the voltage: 12V or 24V

At the same actuator power, a higher voltage means lower current, less loss and less voltage drop, which is why 24V DC dominates industrial control panels. 12V suits on-vehicle and solar setups where the supply already exists. Either way, the supply must cover the start-up peak with margin. Choose a switching supply rated for the surge, and for batteries check capacity and discharge rate. Get the voltage wrong and the cable and fuse have to be redone.

4. Cable size: voltage drop and heating

Undersized cable shows up quickly: the actuator will not reach rated speed, especially over a long run, and the wire gets warm. Check two things: allowable voltage drop, usually 3% to 5% of supply voltage, and current-carrying capacity from a cable table with margin. Count both the feed and return conductors, and keep connectors and terminals no thinner than the cable. Sizing the cable for the actuator power once is cheaper than reworking it later.

5. Fuses and protection: slow-blow is usually right

Start-up current can reach several times the rated value, so a fast-blow fuse nuisance-trips. Choose a slow-blow type that rides through brief surges, rated a little above the maximum running current. Add over-current, reverse-polarity and under-voltage protection where the machine allows it, and prefer a controller with current limiting and soft start to cut the inrush. When several actuators share one supply, protect each branch so one short does not take down the set.

6. Leave margin in the power supply

Do not spec the supply to the sum of the ratings. Leave 20% to 30% for start-up peaks, supply variation and ageing. Watch the temperature range too: many switching supplies derate at high ambient, and outdoor or cold-store machines need a supply that starts reliably when cold. LOUIE Electric Linear Actuator advises treating supply, cable, controller and actuator as one system rather than picking each part in isolation.

7. Common mistakes and a short checklist

Three common mistakes: sizing by actuator power while ignoring the start-up current, so the machine bogs down on start; choosing cable that merely conducts, which brings drop and heat; and fitting whatever fuse is on the shelf, which blows on the first start. A short checklist: work out maximum running current and start-up peak, set the voltage, size cable by voltage drop and current capacity, then choose a slow-blow fuse and leave 20% to 30% supply margin.

Website:Electric Linear Actuators for Medical and Rehabilitation Equipment

Next:Electric Linear Actuator vs Linear Module vs Air Cylinder

13912338006

Online Message

Changzhou Louis Electric Push Rod Co., Ltd.

Company profile  |  Selection table  |  Product display  |  Product application
Copyright:Changzhou Louis Electric Push Rod Co., Ltd.{} Record number:
展开